ESS SE 4.6/5/6KHB

SE 4.6/5/6KHB-60, SE 4.6/5/6KHB-120

Recursos

  • Eficiência máxima de carga/descarga 94%
  • Conveniente para modernizar os sistemas conectados à rede existentes aumentam a proporção de uso espontâneo
  • Com sistema BMS para garantir alta vida útil da bateria
  • Projeto de resfriamento natural
  • Compatível com baterias de chumbo-ácido e energia da bateria de lítio sistemas de armazenamento
  • Configuração e atualização remotas
Model SE 4K6HB-60 SE 4K6HB-120 SE 5KHB-60 SE 5KHB-120 SE 6KHB-60 SE 6KHB-120
Efficiency
Max. efficiency (PV to AC) 97.3%
Max. efficiency (BAT to AC) 94.0%
Input (PV)
Max. PV Power 9000W
Max. PV voltage 550V
Max. input current (input A/input B 15A/15A
Max. short current (input A/input B) 20A/20A
Start operating voltage 90V
MPPT voltage range 70V-520V
No.of MPPT trackers 2
String per MPP tracker 1
Input (BAT)
Compatible battery type Lithium-ion/Lead-acid
Nominal battery voltage 48V
Battery voltage range 40V-60V
Max. charge/discharge current 60A/60A 120A/120A 60A/60A 120A/120A 60A/60A 120A/120A
Max. charge/discharge power 3000W/3000W 5000W/5000W 3000W/3000W 5000W/5000W 3000W/3000W 6000W/6000W
Lithium battery charge curve Self-adaption to BMS
Output (Grid)
Nominal AC output power 4600W 4600W 5000W 5000W 6000W 6000W
Max. AC output apparent power 4600VA 4600VA 5500VA 5500VA 6000VA 6000VA
Max.AC output power (PF=1) 4600W 4600W 5500W 5500W 6000W 6000W
Max. AC output current 22A 22A 25A 25A 27.2A 27.2A
Rated AC voltage 220V
AC voltage range 150V-300V (Adjustable)
Rated grid frequency 50Hz/60Hz
AC frequency range 45Hz-55Hz/55Hz-65Hz (Adjustable)
Grid connecion Single phase
Power factor > 0.99 @rated power (Adjustable 0.8 LD – 0.8 LG)
THDI <3% (Rated Power)
Output (Back up)
Nominal output voltage 230V
Nominal output frequency 50Hz/60Hz
Nominal output power 3000W 4600W 3000W 5000W 3000W 6000W
Nominal output current 13A 20A 13A 21.7A 13A 26A
Transfer time 10ms(typ) / 20ms(max)
THDV <3% @100% R Load
Protection
Protection category Class I
DC switch Support
Anti-islanding protection Support
AC overcurrent protection Support
AC short circuit protection Support
DC reverse connection Support
Surge Arrester DC Type III, AC Type III
Insulation detection Support
Leakage current protection Support
PV overvoltage category II
AC overvoltage category III
General
Max. operation altitude 4000m
Noise emission <35dB
Ingress protection degree IP65
Operating temperature range -25℃~60℃
Relative humidity 0~100%
Cooling concept Natural Cooling
Mounting Wall bracket
Dimensions (W*H*D) 515mm*485mm*175mm
Weight 20Kg 25Kg 20Kg 25Kg 20Kg 25Kg
PV connection way MC4/H4
Battery connection way Dedicated DC connector
AC connection way (grid & back up) Dedicated AC connector
HMI & COM
Display LED+APP
Communication interface RS485/CAN (for BMS), RS485, USB, DRM/RS485 (for Meter), Optional: WiFi/GPRS/LAN
Certification
Grid VDE-AR-N4105, IEC 61727/62116, AS 4777.2, EN 50549-1,G99,CEI 0-21,NRS 097-2-1
Safety IEC 62109-1&2, IEC 62040-1, IEC 62477-1
Warranty 5 Years/10 Years (Optional)