Model | SE 3K6HB-60 | SE 4K6HB-120 | SE 5KHB-120 | SE 6KHB-120 |
Efficiency | ||||
Max. Efficiency (PV to AC) | 97.3% | |||
Eur. Efficiency (PV to AC) | 96.8% | |||
Max. Efficiency (BAT to AC) | 94.3% | |||
Input (PV) | ||||
Max. PV Input Power | 6,300W | 9,000W | ||
Max. PV Voltage | 550V | |||
Start-up Voltage | 90V | |||
MPPT Operating Voltage Range | 70V-540V | |||
Max. Input Current per MPPT | 15A/15A | |||
Max. Short Circuit Current per MPPT | 20A/20A | |||
String per MPPT | 1/1 | |||
Nos. of MPPT | 2 | |||
Input/Output (BAT) | ||||
Battery Type | Lithium-ion / Lead-acid | |||
Nominal Battery Voltage | 48V | |||
Battery Voltage Range | 40V-65V | |||
Max. Charge/Discharge Current | 60A/60A | 120A/120A | 120A/120A | 120A/120A |
Max. Charge/Discharge Power | 3,000W/3,000W | 6,000W/6,000W | 6,000W/6,000W | 6,000W/6,000W |
Output (Grid) | ||||
Nominal AC Output Power | 3,600W | 4,600W | 5,000W | 6,000W |
Max. AC Output Apparent Power | 3,960VA | 4,600VA | 5,500VA | 6,000VA |
Max. AC Output Power (PF=1) | 39,60W | 4,600W | 5,500W | 6,000W |
Max. AC Output Current | 18A | 22A | 25A | 27.2A |
Nominal Grid Voltage | 220V/230V/240V, L+N+PE | |||
Grid Voltage Range | 150V-300V (Adjustable) | |||
Nominal Grid Frequency | 50Hz/60Hz | |||
Grid Frequency Range | 45Hz-55Hz/55Hz-65Hz (Adjustable) | |||
Power Factor | > 0.99 @rated power (Adjustable 0.8 LD – 0.8 LG) | |||
THDI | <3% (Rated Power) | |||
Output (Back up) | ||||
Nominal Output Power | 3,000W | 4,600W | 5,000W | 6,000W |
Nominal Output Current | 13A | 20A | 21.7A | 26A |
Peak Output Apparent Power(>1s) | 4,500VA | 6,900VA | 7,500VA | 9,000VA |
Nominal Output Voltage | 220V/230V/240V, L+N+PE | |||
Nominal Output Frequency | 50Hz/60Hz | |||
Transfer Time | <10ms(typical) | |||
THDV | <3% @100% R Load | |||
Protection | ||||
Protection Category | Class I | |||
DC Switch | Yes | |||
Anti-islanding Protection | Yes | |||
AC Overcurrent Protection | Yes | |||
DC/AC Overvoltage Protection | DC Type II, AC Type III | |||
AC Short Circuit Protection | Yes | |||
DC Reverse Protection | Yes | |||
Surge Arrester | DC Type III, AC Type III | |||
Insulation Resistance Detection | Yes | |||
Leakage Current Protection | Yes | |||
Generator | Optional | |||
General | ||||
Max. Operating Altitude | 4000m (>2000m derating) | |||
Ingress Protection Rating | IP65 | |||
Operating Temperature Range | -25℃~60℃ (>45℃ derating) | |||
Relative Humidity | 0~100% | |||
Cooling Method | Natural Cooling | |||
Mounting | Wall bracket | |||
Dimensions (W*H*D) | 515mm*487mm*175mm | |||
Weight | 16kg | 25kg | ||
PV Connection Way | MC4/H4 | |||
Battery Connection Way | Dedicated DC Connector | |||
AC Connection Way(Grid & Back up) | Dedicated AC Connector | |||
HMI & COM | ||||
Display | Bluetooth & APP + LED , LCD (optional) | |||
Communication Interface | RS485/CAN (for BMS), RS485, USB, Ethernet, DRM/RS485 (for Meter), Optional: Wi-Fi/GPRS/LAN | |||
Certification | ||||
Safety | IEC 62109-1&2,IEC62040-1,IEC 62477-1 | |||
Grid | VDE 4105, I EC 61727/62116, AS 4777.2, EN 50549-1, C10/11, G98/G99/G100, CEI 0-21, NRS 097-2-1, RD 1699/661/647/413,UNE 217002, | |||
Warranty | 5 Years |